% Skapad med Modbus Creator % - OBS! Användaren ansvarar själv för att samma TYPID inte används flera gånger i samma apparat. % TYPID 10000-19999 är för användardefinierade enheter DEVICETYPE SwegonCASA NAMED "SwegonCASA" TYPEID 15033 IS PARAMETER Id : "Adress"; V17 : "wOpMode" [""]; % 0=Away, 1=Normal, 2=Boost V18 : "wSupplyTempSP" ["°C"]DEC1; V19 : "wClearAlarms" [""]; % 1 = FreezingDanger 2 = ServiceReminderUser 3 = ServiceReminderService 4 = IRSensorFailure 5 =TemperatureDeviation 6 = Efficiency 7 = FanFailureSupply 8 = FanFailureExhaust 9 = OverheatProtection 10 = FilterGuard 11 = TempSensorError PUBLIC V1 : "OpMode" [""]; % 0=Away, 1=Normal, 2=Boost V2 : "UnitState" [""]; % 0=Stopped, 1=Running V3 : "SupplyTempSP" ["°C"]DEC1; V4 : "TempT3" ["°C"]DEC1; V5 : "TempT4" ["°C"]DEC1; V6 : "HREefficiency" ["%"]; V7 : "IR failure" [""]; % 0=Off, 1=Alarm V8 : "TempDeviation" [""]; % 0=Off, 1=Alarm V9 : "FreezeDanger" [""]; % 0=Off, 1=Alarm V10 : "FilterGuard" [""]; % 0=Off, 1=Alarm V11 : "OverheatAHeater" [""]; % 0=Off, 1=Alarm V12 : "Efficiency" [""]; % 0=Off, 1=Alarm V13 : "FanFailureSA" [""]; % 0=Off, 1=Alarm V14 : "FanFailEA" [""]; % 0=Off, 1=Alarm V15 : "Service" [""]; % 0=Off, 1=Alarm V16 : "TempSensor" [""]; % 0=Off, 1=Alarm PRIVATE count3; count4; count6; tmp; BAUDRATE 9600; CHECKSUM MODBUS SWAPPED; TELEGRAM Read3 NAMED "Read 3" IS QUESTION DATA[0] := BYTE(Id); % Enhetens Modbus adress DATA[1] := HEX(03); % Modbus kommando för att läsa register DATA[2] <- RWORD( IF(count3>2) THEN count3 := 0; ENDIF; IF (count3=0) THEN tmp := 4100; ELSIF (count3=1) THEN tmp := 8000; ELSIF (count3=2) THEN tmp := 8003; ENDIF; DATA:= tmp; ); DATA[4] := RWORD(01); ANSWER SIZE 7 DATA[0] = BYTE(Id); DATA[1] = BYTE(03); DATA[3] -> RWORD( IF (count3=0) THEN V1 := DATA; ELSIF (count3=1) THEN V2 := DATA; ELSIF (count3=2) THEN V3 := DATA/10; ENDIF; count3 := count3+1; ); TIMEOUT 300 END; TELEGRAM Read4 NAMED "Read 4" IS QUESTION DATA[0] := BYTE(Id); % Enhetens Modbus adress DATA[1] := HEX(04); % Modbus kommando för att läsa register DATA[2] <- RWORD( IF(count4>12) THEN count4 := 0; ENDIF; IF (count4=0) THEN tmp := 335; ELSIF (count4=1) THEN tmp := 336; ELSIF (count4=2) THEN tmp := 341; ELSIF (count4=3) THEN tmp := 366; ELSIF (count4=4) THEN tmp := 367; ELSIF (count4=5) THEN tmp := 368; ELSIF (count4=6) THEN tmp := 369; ELSIF (count4=7) THEN tmp := 370; ELSIF (count4=8) THEN tmp := 371; ELSIF (count4=9) THEN tmp := 372; ELSIF (count4=10) THEN tmp := 373; ELSIF (count4=11) THEN tmp := 374; ELSIF (count4=12) THEN tmp := 375; ENDIF; DATA:= tmp; ); DATA[4] := RWORD(01); ANSWER SIZE 7 DATA[0] = BYTE(Id); DATA[1] = BYTE(04); DATA[3] -> RWORD( IF (count4=0) THEN V4 := DATA/10; ELSIF (count4=1) THEN V5 := DATA/10; ELSIF (count4=2) THEN V6 := DATA; ELSIF (count4=3) THEN V7 := DATA; ELSIF (count4=4) THEN V8 := DATA; ELSIF (count4=5) THEN V9 := DATA; ELSIF (count4=6) THEN V10 := DATA; ELSIF (count4=7) THEN V11 := DATA; ELSIF (count4=8) THEN V12 := DATA; ELSIF (count4=9) THEN V13 := DATA; ELSIF (count4=10) THEN V14 := DATA; ELSIF (count4=11) THEN V15 := DATA; ELSIF (count4=12) THEN V16 := DATA; ENDIF; count4 := count4+1; ); TIMEOUT 300 END; TELEGRAM WriteRegister NAMED "Write Register" IS QUESTION DATA[0] := BYTE(Id); % Enhetens Modbus adress DATA[1] := HEX(06); % Modbus kommando för att skriva ett register DATA[2] <- RWORD( IF(count6>2) THEN count6 := 0; ENDIF; IF (count6=0) THEN DATA := 4100; ELSIF (count6=1) THEN DATA := 8003; ELSIF (count6=2) THEN DATA := 8028; ENDIF; ); % Register adress DATA[4] <- RWORD( IF (count6=0) THEN DATA := V17; ELSIF (count6=1) THEN DATA := V18*10; ELSIF (count6=2) THEN DATA := V19; ENDIF; count6 := count6+1; ); ANSWER SIZE 8 DATA[0] = BYTE(Id); DATA[1] = BYTE(06); TIMEOUT 300 END; END;