Siox RO2 via ES2

Detaljer

Typ
Drivrutin
Upplaggd av
Ove Jansson, Abelko Innovation
Version
1
Uppdaterad
2018-09-26
Skapad
2018-09-26
Kategori
IO enheter, Modbus, Övriga protokoll
Visningar
1754

Beskrivning

.

Bruksanvisning

.

Juridisk information

Alla skript tillhandahålls i befintligt skick och all användning sker på eget ansvar. Felaktig använding kan leda till skadad eller förstörd utrustning.

Skript kod

DEVICETYPE R02 NAMED "Siox R02" TYPEID 18379 IS

 PARAMETER
  Id : "Adress" [""]INT;

 PUBLIC
  OP1 : "AI1 range 2-10 V / 0,4-2 V / 4-20 mA Range" ["No,Yes"]ENUM;
  OP2 : "AI2 range 2-10 V / 0,4-2 V / 4-20 mA Range" ["No,Yes"]ENUM;
  OP1b : "AI1 Potentiometer Linearization 0-20 kS" ["No,Yes"]ENUM;
  OP2b : "AI2 Potentiometer Linearization 0-20 kS" ["No,Yes"]ENUM;
  OP1c : "AI1 0-2 V Range" ["No,Yes"]ENUM;
  OP2c : "AI2 0-2 V Range" ["No,Yes"]ENUM;
  OP1d : "AI1 NTC Temperature Linearization -50 - +150 °C" ["No,Yes"]ENUM;
  OP2d : "AI2 NTC Temperature Linearization -50 - +150 °C" ["No,Yes"]ENUM;
  OP1e : "AI1 0-20 mA Range" ["No,Yes"]ENUM;
  OP2e : "AI2 0-20 mA Range" ["No,Yes"]ENUM;
  OP1f : "AI1 0-10 V Range" ["No,Yes"]ENUM;
  OP2f : "AI2 0-10 V Range" ["No,Yes"]ENUM;
  OP1g : "AO1 Digital Output 24 V 20 mA" ["No,Yes"]ENUM;
  OP2g : "AO2 Digital Output 24 V 20 mA" ["No,Yes"]ENUM;
  OP1h : "AO1 2-10 V (4-20 mA for R02-2)" ["No,Yes"]ENUM;
  OP2h : "AO2 2-10 V (4-20 mA for R02-2)" ["No,Yes"]ENUM;
  OP1i : "AO1 0-10 V (4-20 mA for R02-2)" ["No,Yes"]ENUM;
  OP2i : "AO2 0-10 V (4-20 mA for R02-2)" ["No,Yes"]ENUM;
  DI1 : "DigitalInput 1" INT;
  DI2 : "DigitalInput 2" INT;
  AI1 : "AnalogInput 1" [""]INT;
  AI2 : "AnalogInput 2" [""]INT;
  AO1 : "AnalogOutput 1" ["%"]DEC2;
  AO2 : "AnalogOutput 2" ["%"]DEC2;
  C1 : "Counter 1" [""]INT;
  C2 : "Counter 2" [""]INT;

 PRIVATE
  tmp;
 BAUDRATE 9600;
 CHECKSUM MODBUS SWAPPED;

 TELEGRAM Read4 NAMED "Read 4" IS
  QUESTION
   DATA[0] := BYTE(Id); % Enhetens Modbus adress
   DATA[1] :=  HEX(03); 
   DATA[2] := RWORD(0); % Start address
   DATA[4] := RWORD(28); % Antal register att läsa
  ANSWER SIZE 61 % (Antal register * 2) + 5
   DATA[0] = BYTE(Id);
   DATA[1] = HEX(03);
   DATA[2] = BYTE(56); % Antal Bytes
   DATA[11] -> BYTE( %4
    IF DATA & 64 THEN tmp:=1; ELSE tmp:=0; ENDIF; OP1:=tmp;
    IF DATA = 40 THEN tmp:=1; ELSE tmp:=0; ENDIF; OP1b:=tmp;
    IF DATA = 32 THEN tmp:=1; ELSE tmp:=0; ENDIF; OP1c:=tmp;
    IF DATA = 24 THEN tmp:=1; ELSE tmp:=0; ENDIF; OP1d:=tmp;
    IF DATA = 8 THEN tmp:=1; ELSE tmp:=0; ENDIF; OP1e:=tmp;
    IF DATA = 0 THEN tmp:=1; ELSE tmp:=0; ENDIF; OP1f:=tmp;
   );   
   DATA[12] -> BYTE( %4
    IF DATA & 128 THEN tmp:=1; ELSE tmp:=0; ENDIF; OP1g:=tmp;
    IF DATA & 64 THEN tmp:=1; ELSE tmp:=0; ENDIF; OP1h:=tmp;
    IF DATA > 15 THEN tmp:=0; ELSE tmp:=1; ENDIF; OP1i:=tmp;
   );   
   DATA[13] -> BYTE( %5
    IF DATA & 64 THEN tmp:=1; ELSE tmp:=0; ENDIF; OP2:=tmp;
    IF DATA = 40 THEN tmp:=1; ELSE tmp:=0; ENDIF; OP2b:=tmp;
    IF DATA = 32 THEN tmp:=1; ELSE tmp:=0; ENDIF; OP2c:=tmp;
    IF DATA = 24 THEN tmp:=1; ELSE tmp:=0; ENDIF; OP2d:=tmp;
    IF DATA = 8 THEN tmp:=1; ELSE tmp:=0; ENDIF; OP2e:=tmp;
    IF DATA = 0 THEN tmp:=1; ELSE tmp:=0; ENDIF; OP2f:=tmp;
   );   
   DATA[14] -> BYTE( %4
    IF DATA & 128 THEN tmp:=1; ELSE tmp:=0; ENDIF; OP2g:=tmp;
    IF DATA & 64 THEN tmp:=1; ELSE tmp:=0; ENDIF; OP2h:=tmp;
    IF DATA > 15 THEN tmp:=0; ELSE tmp:=1; ENDIF; OP2i:=tmp;
   );   
   DATA[21] -> RWORD(
    IF DATA & 1 THEN tmp:=1; ELSE tmp:=0; ENDIF; DI1:=tmp;
    IF DATA & 2 THEN tmp:=1; ELSE tmp:=0; ENDIF; DI2:=tmp;
   );
   DATA[27] -> RWORD(AO1:=(DATA/4096)*100;);
   DATA[29] -> RWORD(AO2:=(DATA/4096)*100;);
   DATA[31] -> RWORD(AI1:=DATA;); % 32768 - 32767
   DATA[33] -> RWORD(AI2:=DATA;); 
   DATA[51] -> RWORD32(C1:=DATA;);
   DATA[55] -> RWORD32(C2:=DATA;);
  TIMEOUT 800